TCHD-Z500-6000W Net Inverters
- Courier
- In detail
- BrandTONTRUHUDA
- Country of manufactureChina
Characteristics:
1.pure sine wave output
2.CPU management,intelligent control,modular composition
3. With LED display which can directly display all the operating parameters of machine.
4.High converting efficiency which is between 89% ~ 98%,low waste,between 1W~ 6W in the sleep state.
5.It can charge for different types of battery.such as sealed lead-acid batteries, open type lead acid batteries,gel batteries etc.
Annotation:Before Lithium batteries leave factory,they need to be set up according to specifications required by customer.
6.It adopts intelligent charging for any kinds of batteries . The max charging current is adjustable . It could be used alone as charger, and could be modulated to MAX70A
7.This series of products have strong load carrying capacity and anti load capacity. It can drive the pump ,air conditioning, refrigerator, etc.
8.The products adopt the latest USA power frequency circuit design,using new imported electronic materials,With good system stability, low failure rate, long using life which could be above to 8 years.
8.Perfect protection:low voltage,high voltage,great heat,short circuit,overload etc.
9.It passed CE,EMC and other international certifications.
10.Product warranty period is 2 years,Lifelong technical support.
Parameter : Commercial power supply mode | |||
220V system | 110V system | ||
Efficiency | ≥98% | ||
Input voltage waveform | Pure sine wave
(grid power or generator) |
Pure sine wave
(grid power or generator) |
|
Rated input voltage | 220Vac | 110Vac | |
Rated output voltage (V) | 220Vac | 110Vac | |
Low voltage disconnect | 184Vac±4% | 92Vac±4% | |
Low voltage recovery | 194Vac ±4% | 97Vac ±4% | |
Over voltage disconnect | 253Vac±4% | 127Vac±4% | |
Over voltage recovery | 243Vac±4% | 122Vac±4% | |
Rated input frequency | 50Hz/ 60Hz (Auto-detect) | 50Hz/ 60Hz (Auto-detect) | |
Output voltagewaveform | same as the
input voltage waveform |
Same as the
input voltage waveform |
|
Transfer time(Ac to Dc) | <10ms | <10ms | |
Transfer time (Dc to Ac) | <10ms | <10ms | |
Specification: Inverter mode | |||
Power factor | 0~1.0 | ||
Rated output voltage (V) | 230Vac | 110Vac | |
Rated output frequency(Hz) | 50Hz ± 0.3Hz/60Hz ± 0.3Hz | ||
Output voltage range | ±10% rms | ||
Frequency | >87% | ||
Over load protection
(SMPS load) |
(110%<Load<125%) ±10%: Disconnect the output after 15minutes
(125%<Load<150%) ±10%: Disconnect the output voltage after 10s Load >150% ±10%: Disconnect output voltage after 0.2s |
||
Under voltage alarming | 10.5Vdc ± 0.3Vdc (12V )
21.0Vdc ± 0.6Vdc (24V )42.0Vdc ± 1.2Vdc (48V ) |
||
Low DC input voltage auto-disconnect | 10.0Vdc ± 0.3Vdc(12V )
20.0vdc± 0.6Vdc (24V )40.0vdc± 1.2Vdc (48V ) |
||
Input over voltage
alarming &Outage |
16Vdc ± 0.3Vdc (12V )
32Vdc ± 0.6Vdc (24V )64Vdc ± 1.2Vdc (48V ) |
||
Input over voltage recovery | 15.5Vdc ± 0.3Vdc(12V )
31.0Vdc ± 0.6Vdc (24V )62.0Vdc ± 1.2Vdc (48V ) |
||
Power-saving mode | No load power≦25W | ||
Charge regulation | |||
Regulation | Three stages: | ||
Constant current charge(Constant current stage)→
Constant voltage charge(constant voltage stage)→ Floating charge(constant voltage stage) |
|||
Security Certification:CE(EN62040-1) EMC :EN62040-2, C2 | |||
Communication interface | RS232/USB(Customized) | ||
Cooling | Variable-speed fan under ventilation condition | ||
Operating environment ,noisy | Environment temperature,humidity0-40℃,
0-95% Relative humidity(no condensation);Noisy<60dB |
||
Net Weight(KG) | 15(1KW)、20(2KW)、24.5(3KW)、36(4KW)、42(5KW)、49(6KW) | ||
Dimension: | 425*188*168 622*188*168
Installing dimension:480*232*188 678*232*188 |